ABB REC670 Applications Manual page 229

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
Bay control REC670 2.2 ANSI
Application manual
Mode: The voltage and current used for the power measurement. The setting
possibilities are shown in table 27.
Table 27:
Complex power calculation
Mode
Set value
A,B,C
Arone
PosSeq
A,B
B,C
C,A
A
B
C
The function has two stages that can be set independently.
With the parameter OpMode1(2) the function can be set Enabled/Disabled.
The function gives trip if the power component in the direction defined by the setting
Angle1(2) is larger than the set pick up power value Power1(2)
Current protection
Formula used for complex power calculation
*
*
=
×
+
×
S
V
I
V
I
A
A
B
B
EQUATION2038 V1 EN-US
*
-
=
×
×
S
V
I
V
AB
A
BC
EQUATION2039 V1 EN-US
*
= ×
×
S
3 V
I
PosSeq
PosSeq
EQUATION2040 V1 EN-US
*
*
-
=
×
)
S
V
(I
I
AB
A
B
EQUATION2041 V1 EN-US
*
*
-
=
×
)
S
V
(I
I
B
C
BC
EQUATION2042 V1 EN-US
*
*
-
=
×
)
S
V
(I
I
CA
C
A
EQUATION2043 V1 EN-US
*
= ×
×
S 3 V
I
A
A
EQUATION2044 V1 EN-US
*
= ×
×
S
3 V
I
B
B
EQUATION2045 V1 EN-US
*
= ×
×
S
3 V
I
C
C
EQUATION2046 V1 EN-US
Section 8
*
+
×
V
I
C
C
(Equation 77)
*
I
C
(Equation 78)
(Equation 79)
(Equation 80)
(Equation 81)
(Equation 82)
(Equation 83)
(Equation 84)
(Equation 85)
223