Underfrequency Protection Saptuf (81) - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
Section 10
10.1
10.1.1
10.1.2
Bay control REC670 2.2 ANSI
Application manual
Frequency protection

Underfrequency protection SAPTUF (81)

Identification
Function description
Underfrequency protection
Application
Underfrequency protection SAPTUF (81) is applicable in all situations, where reliable
detection of low fundamental power system frequency is needed. The power system
frequency, and the rate of change of frequency, is a measure of the unbalance between
the actual generation and the load demand. Low fundamental frequency in a power
system indicates that the available generation is too low to fully supply the power
demanded by the load connected to the power grid. SAPTUF (81) detects such
situations and provides an output signal, suitable for load shedding, generator boosting,
HVDC-set-point change, gas turbine start up and so on. Sometimes shunt reactors are
automatically switched in due to low frequency, in order to reduce the power system
voltage and hence also reduce the voltage dependent part of the load.
SAPTUF (81) is very sensitive and accurate and is used to alert operators that
frequency has slightly deviated from the set-point, and that manual actions might be
enough. The underfrequency signal is also used for overexcitation detection. This is
especially important for generator step-up transformers, which might be connected to
the generator but disconnected from the grid, during a roll-out sequence. If the
generator is still energized, the system will experience overexcitation, due to the low
frequency.
Frequency protection
IEC 61850
IEC 60617
identification
identification
SAPTUF
f <
SYMBOL-P V1 EN-US
Section 10
IP15746-1 v3
M14865-1 v5
ANSI/IEEE C37.2
device number
81
M13350-3 v4
259