Setting Guidelines - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
14.7.3
14.8
14.8.1
14.8.2
Bay control REC670 2.2 ANSI
Application manual
VSGAPC
PSTO
INTONE
IPOS1
IPOS2
NAM_POS1
Disabled
NAM_POS2
Enabled
ANSI07000112 V3 EN-US
Figure 185:
Control of Autorecloser from local HMI through Selector mini switch
VSGAPC is also provided with IEC 61850 communication so it can be controlled from
SA system as well.

Setting guidelines

Selector mini switch (VSGAPC) function can generate pulsed or steady commands (by
setting the Mode parameter). When pulsed commands are generated, the length of the
pulse can be set using the tPulse parameter. Also, being accessible on the single line
diagram (SLD), this function block has two control modes (settable through CtlModel):
Dir Norm and SBO Enh.
Generic communication function for Double Point
indication DPGAPC
Identification
Function description
Generic communication function for
Double Point indication
Application
Generic communication function for Double Point indication (DPGAPC) function
block is used to send double point position indication to other systems, equipment or
functions in the substation through IEC 61850-8-1 or other communication protocols.
CMDPOS12
ON
CMDPOS21
OFF
IEC 61850
IEC 60617
identification
identification
DPGAPC
Section 14
Control
INV
OUT
INPUT
SMBRREC_79
SETON
ANSI07000112-3-en.vsd
SEMOD158807-4 v4
SEMOD55384-1 v4
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
ANSI/IEEE C37.2
device number
-
-
SEMOD55391-5 v8
457