Delta Blocking Scheme - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
15.1.3.2
15.1.3.3
15.1.3.4
15.1.3.5
Bay control REC670 2.2 ANSI
Application manual

Delta blocking scheme

Operation
Enabled
Set
=
Set
SchemeType
=
DeltaBlocking
tCoord
Set
= 0 s
tSendMin
Set
= 0 s
Unblock
Disabled
Set
=
(Set to
used.
Set to
tSecurity
Set
= 0.035 s
DeltaI
Set
= 10 %IB
Set
DeltaV
= 5 %VB
Delta3I0
Set
= 10 %IB
Delta3V0
Set
= 5 %VB
Permissive underreaching scheme
Operation
Enabled
Set
=
SchemeType
Permissive UR
Set
=
Set
tCoord
= 0 ms
tSendMin
Set
= 0.1 s
Unblock
Disabled
Set
=
tSecurity
Set
= 0.035 s
Permissive overreaching scheme
Operation
Enabled
Set
=
Set
Scheme type
=
Permissive OR
tCoord
Set
= 0 ms
tSendMin
Set
= 0.1 s (0 s in parallel line applications)
Unblock
Disabled
Set
=
Set
tSecurity
= 0.035 s
Unblocking scheme
Set
Unblock
=
Restart
(Loss of guard signal will give both trip and alarm
Choose
tSecurity
Set
= 0.035 s
NoRestart if Unblocking scheme with no alarm for loss of guard is to be
Restart if Unblocking scheme with alarm for loss of guard is to be used)
NoRestart if only trip is required)
Section 15
Scheme communication
GUID-F4359690-F433-46CB-A173-8C14559E3FCF v1
M13869-25 v4
M13869-34 v4
M13869-43 v4
473