Identification

Function description
Integer to boolean 16 conversion with
logic node representation
Application
Integer to boolean 16 conversion with logic node representation function (ITBGAPC)
is used to transform an integer into a set of 16 boolean signals. ITBGAPC function can
receive an integer from a station computer – for example, over IEC 61850–8–1. This
function is very useful when the user wants to generate logical commands (for selector
switches or voltage controllers) by inputting an integer number. ITBGAPC function
has a logical node mapping in IEC 61850.
The Integer to Boolean 16 conversion with logic node representation function
(ITBGAPC) will transfer an integer with a value between 0 to 65535 communicated
via IEC 61850 and connected to the ITBGAPC function block to a combination of
activated outputs OUTx where 1≤x≤16.
The values of the different OUTx are according to the Table 45.
If the BLOCK input is activated, it freezes the logical outputs at the last value.
Table 45:
Output signals
Name of OUTx
Type
OUT1
BOOLEAN
OUT2
BOOLEAN
OUT3
BOOLEAN
OUT4
BOOLEAN
OUT5
BOOLEAN
OUT6
BOOLEAN
OUT7
BOOLEAN
OUT8
BOOLEAN
OUT9
BOOLEAN
OUT10
BOOLEAN
OUT11
BOOLEAN
OUT12
BOOLEAN
OUT13
BOOLEAN
Table continues on next page
IEC 61850
IEC 60617
identification
identification
ITBGAPC
-
Description
Value when
activated
Output 1
1
Output 2
2
Output 3
4
Output 4
8
Output 5
16
Output 6
32
Output 7
64
Output 8
128
Output 9
256
Output 10
512
Output 11
1024
Output 12
2048
Output 13
4096
1MRK 511 401-UUS A
SEMOD167944-2 v4
ANSI/IEEE C37.2
device number
-
SEMOD158512-5 v7
Value when
deactivated
0
0
0
0
0
0
0
0
0
0
0
0
0
Bay control REC670 2.2 ANSI