1MRK 511 401-UUS A
17.5.3
17.6
Bay control REC670 2.2 ANSI
Application manual
Setting guidelines
The input parameters for the Event function (EVENT) can be set individually via the
local HMI (Main Menu/Settings / IED Settings / Monitoring / Event Function) or
via the Parameter Setting Tool (PST).
EventMask (Ch_1 - 16)
The inputs can be set individually as:
•
NoEvents
•
OnSet, at pick-up of the signal
•
OnReset, at drop-out of the signal
•
OnChange, at both pick-up and drop-out of the signal
•
AutoDetect, the EVENT function makes the reporting decision (reporting criteria
for integers have no semantic, prefer to be set by the user)
LONChannelMask or SPAChannelMask
Definition of which part of the event function block that shall generate events:
•
Disabled
•
Channel 1-8
•
Channel 9-16
•
Channel 1-16
MinRepIntVal (1 - 16)
A time interval between cyclic events can be set individually for each input channel.
This can be set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that
is, no cyclic communication.
It is important to set the time interval for cyclic events in an optimized
way to minimize the load on the station bus.
Disturbance report DRPRDRE
Section 17
Monitoring
IP14841-1 v1
M12811-3 v3
M12811-5 v3
M12811-15 v2
M12811-29 v3
M12811-34 v1
IP14584-1 v2
531