Bay control REC670 2.2 ANSI
Application manual

Summation block 3 phase 3PHSUM

Application
The analog summation block 3PHSUM function block is used in order to get the sum
of two sets of 3 phase analog signals (of the same type) for those IED functions that
might need it.
Setting guidelines
The summation block receives the three-phase signals from SMAI blocks. The
summation block has several settings.
SummationType: Summation type (Group 1 + Group 2, Group 1 - Group 2, Group 2 -
Group 1 or –(Group 1 + Group 2)).
DFTReference: The reference DFT block (InternalDFT Ref,DFTRefGrp1 or External
DFT ref) .
FreqMeasMinVal: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of VBasebase voltage setting (for each instance x).
GlobalBaseSel: Selects the global base value group used by the function to define
(IBase), (VBase) and (SBase).
Global base values GBASVAL
Identification
Function description
Global base values
IEC 61850
IEC 60617
identification
identification
GBASVAL
-
Section 23
Basic IED functions
SEMOD55968-1 v2
SEMOD56004-4 v3
SEMOD56006-4 v6
GUID-2FDB0A2C-10FE-4954-B6E4-9DA2EEEF1668 v1
GUID-0D5405BE-E669-44C8-A208-3A4C86D39115 v3
ANSI/IEEE C37.2
device number
-
611