Application - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 17
Monitoring
17.7.2
17.7.3
17.8
17.8.1
17.8.2
540

Application

The Logical signal status report (BINSTATREP) function makes it possible to poll
signals from various other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs and
can be read from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the input
signal remains set for a longer period, the output will remain set until the input signal
resets.
INPUTn
OUTPUTn
IEC09000732 V1 EN-US
Figure 212:
BINSTATREP logical diagram
Setting guidelines
The pulse time t is the only setting for the Logical signal status report (BINSTATREP).
Each output can be set or reset individually, but the pulse time will be the same for all
outputs in the entire BINSTATREP function.
Fault locator LMBRFLO
Identification
Function description
Fault locator
Application
The main objective of line protection and monitoring IEDs is fast, selective and
reliable operation for faults on a protected line section. Besides this, information on
t
IEC09000732-1-en.vsd
IEC 61850
IEC 60617
identification
identification
LMBRFLO
-
1MRK 511 401-UUS A
GUID-F9D225B1-68F7-4D15-AA89-C9211B450D19 v3
t
GUID-BBDA6900-4C1A-4A7C-AEA5-3C49C2749254 v2
ANSI/IEEE C37.2
device number
-
Bay control REC670 2.2 ANSI
Application manual
IP14592-1 v2
M14892-1 v3
M13752-3 v6