ABB REC670 Applications Manual page 533

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
Bay control REC670 2.2 ANSI
Application manual
100000
50000
20000
10000
5000
2000
1000
500
200
100
50
20
10
0.1
0.2
0.5
1
Interrupted current (kA)
IEC12000623 V1 EN-US
Figure 210:
An example for estimating the remaining life of a circuit breaker
Calculation for estimating the remaining life
The graph shows that there are 10000 possible operations at the rated operating current
and 900 operations at 10 kA and 50 operations at rated fault current. Therefore, if the
interrupted current is 10 kA, one operation is equivalent to 10000/900 = 11 operations
at the rated current. It is assumed that prior to tripping, the remaining life of a breaker
is 10000 operations. Remaining life calculation for three different interrupted current
conditions is explained below.
Breaker interrupts at and below the rated operating current, that is, 2 kA, the
remaining life of the CB is decreased by 1 operation and therefore, 9999
operations remaining at the rated operating current.
Breaker interrupts between rated operating current and rated fault current, that is,
10 kA, one operation at 10kA is equivalent to 10000/900 = 11 operations at the
P1
2
5
10
20
50
100
IEC12000623_1_en.vsd
Section 17
Monitoring
P2
527

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents