Section 14
Control
Table 39:
Setting of TxRXOP
TrfId=T1
T1RXOP=
Off
TrfId=T2
T1RXOP=
On
TrfId=T3
T1RXOP=
On
432
SetV
VCTRStatus
X2
The transformers controlled in parallel with the circulating current method or the
master-follower method must be assigned unique identities. These identities are
entered as a setting in each TR8ATCC (90), and they are predefined as T1, T2, T3,...,
T8 (transformers 1 to 8). In figure
TrfId set to T1, T2 and T3, respectively.
For parallel control with the circulating current method or the master-follower method
alternatively, the same type of data set as described above, must be exchanged between
two TR8ATCC (90). To achieve this, each TR8ATCC (90) is transmitting its own data
set on the output ATCCOUT as previously mentioned. To receive data from the other
transformers in the parallel group, the output ATCCOUT from each transformer must
be connected (via GOOSE or internally in the application configuration) to the inputs
HORIZx (x = identifier for the other transformers in the parallel group) on TR8ATCC
(90) function block. Apart from this, there is also a setting in each TR8ATCC =/,..., =/
T1RXOP=Off/On,..., T8RXOP=Off/ On. This setting determines from which of the
other transformer individuals that data shall be received. Settings in the three
TR8ATCC blocks for the transformers in figure 179, would then be according to the
table 39:
T2RXOP=
T3RXOP=
On
On
T2RXOP=
T3RXOP=
Off
On
T2RXOP=
T3RXOP=
On
Off
Observe that this parameter must be set to Disabled for the "own" transformer. (for
transformer with identity T1 parameter T1RXOP must be set to Disabled, and so on.
Blocking
Blocking conditions
The purpose of blocking is to prevent the tap changer from operating under conditions
that can damage it, or otherwise when the conditions are such that power system
related limits would be exceeded or when, for example the conditions for automatic
control are not met.
179
there are three transformers with the parameter
T4RXOP=
T5RXOP=
Off
Off
T4RXOP=
T5RXOP=
Off
Off
T4RXOP=
T5RXOP=
Off
Off
1MRK 511 401-UUS A
T6RXOP=
T7RXOP=
Off
Off
T6RXOP=
T7RXOP=
Off
Off
T6RXOP=
T7RXOP=
Off
Off
Bay control REC670 2.2 ANSI
T8RXOP=
Off
T8RXOP=
Off
T8RXOP=
Off
SEMOD159053-275 v2
SEMOD159053-277 v6
Application manual