Line application example

Four step residual overcurrent protection can be used in different ways. Below is
described one application possibility to be used in meshed and effectively grounded
systems.
The protection measures the residual current out on the protected line. The protection
function has a directional function where the polarizing voltage (zero-sequence
voltage) is the polarizing quantity.
The polarizing voltage and current can be internally generated when a three-phase set
of voltage transformers and current transformers are used.
ö
÷
÷
+
×
B
TD
÷
÷
ø
1MRK 511 401-UUS A
(Equation 38)
M15282-184 v8
Bay control REC670 2.2 ANSI
Application manual