Section 14
Control
388
Signal
S1S2OPTR
No bus-section coupler connection between bus-sections 1 and 2.
VPS1S2TR
The switch status of bus-section coupler BS is valid.
EXDU_BS
No transmission error from the bay that contains the above information.
For a bus-section circuit breaker between A1 and A2 section busbars, these conditions
are valid:
S1S2OPTR (B1B2)
BC12OPTR (sect.1)
1289OPTR (bay 1/sect.2)
. . .
. . .
1289OPTR (bay n/sect.2)
S1S2OPTR (B1B2)
BC12OPTR (sect.2)
1289OPTR (bay 1/sect.1)
. . .
. . .
1289OPTR (bay n /sect.1)
VPS1S2TR (B1B2)
VPBC12TR (sect.1)
VP1289TR (bay 1/sect.2)
. . .
. . .
VP1289TR (bay n/sect.1)
VPBC12TR (sect.2)
VP1289TR (bay 1/sect.1)
. . .
. . .
VP1289TR (bay n/sect.1)
EXDU_BS (B1B2)
EXDU_BC (sect.1)
EXDU_12 (bay 1/sect.2)
. . .
. . .
EXDU_12 (bay n /sect.2)
EXDU_BC (sect.2)
EXDU_12(bay 1/sect.1)
. . .
. . .
EXDU_12 (bay n /sect.1)
ANSI04000490 V1 EN-US
Figure 144:
Signals from any bays for a bus-section circuit breaker between
sections A1 and A2
OR
AND
AND
BBTR_OP
OR
AND
AND
VP_BBTR
AND
EXDU_12
en04000490_ansi.vsd
1MRK 511 401-UUS A
Bay control REC670 2.2 ANSI
Application manual