Signals In Breaker And A Half Arrangement - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
14.4.7.4
Bay control REC670 2.2 ANSI
Application manual
Signal
189OPTR
189 is open.
289OPTR
289 is open.
VP189TR
The switch status of 189 is valid.
VP289TR
The switch status of 289 is valid.
EXDU_DB
No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.
For B1B2_DC, corresponding signals from busbar B are used. The same type of
module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnectors A1A2_DC and B1B2_DC.
Signal
DCOPTR
The bus-section disconnector is open.
VPDCTR
The switch status of bus-section disconnector DC is valid.
EXDU_DC
No transmission error from the bay that contains the above information.
The logic is identical to the double busbar configuration described in section "Signals
in single breaker arrangement".

Signals in breaker and a half arrangement

The busbar grounding switch is only allowed to operate if all disconnectors of the bus-
section are open.
Section 1
(WA1)A1
(WA2)B1
A1A2_DC(BS)
B1B2_DC(BS)
BB_ES
BH_LINE
ANSI04000512 V1 EN-US
Figure 166:
Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic are the same as for the logic for the double busbar
configuration described in section "Signals in single breaker arrangement".
Signal
BB_DC_OP
All disconnectors on this part of the busbar are open.
VP_BB_DC
The switch status of all disconnectors on this part of the busbar is valid.
EXDU_BB
No transmission error from any bay that contains the above information.
Section 2
A2
B2
BB_ES
BH_LINE
en04000512_ansi.vsd
Section 14
Control
M15053-123 v4
403