Section 5
Local HMI
5.4.3
100
Numerical values are presented either in integer or in decimal format with minimum
and maximum values. Character strings can be edited character by character.
Enumerated values have a predefined set of selectable values.

Front communication

The RJ-45 port in the LHMI enables front communication.
The green uplink LED on the left is lit when the cable is successfully connected to
the port.
The yellow LED is not used; it is always off.
IEC13000280-1-en.vsd
GUID-94AF2358-6905-4782-B37B-ACD3DCBF7F9C V1 EN-US
Figure 31:
RJ-45 communication port and green indicator LED
1 RJ-45 connector
2 Green indicator LED
The default IP address for the IED front port is 10.1.150.3 and the corresponding
subnetwork mask is 255.255.254.0. It can be set through the local HMI path Main
menu/Configuration/Communication/Ethernet configuration/FRONT port/
AP_FRONT.
Do not connect the IED front port to a LAN. Connect only a single
local PC with PCM600 to the front port. It is only intended for
temporary use, such as commissioning and testing.
2
1
1MRK 511 401-UUS A
GUID-FD72A445-C8C1-4BFE-90E3-0AC78AE17C45 v11
Bay control REC670 2.2 ANSI
Application manual