Interlocking For Transformer Bay Ab_Trafo (3) - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
14.4.4
14.4.4.1
Bay control REC670 2.2 ANSI
Application manual
7189G_OP = 1
7189G_CL = 0
If there is no second busbar B and therefore no 289 and 2089 disconnectors, then the
interlocking for 289 and 2089 are not used. The states for 289, 2089, 2189G, BC_12,
BBTR are set to open by setting the appropriate module inputs as follows. In the
functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
289_OP = 1
289_CL = 0
2089_OP = 1
2089_CL = 0
2189G_OP = 1
2189G_CL = 0
BC_12_CL = 0
VP_BC_12 = 1
BBTR_OP = 1
VP_BBTR = 1

Interlocking for transformer bay AB_TRAFO (3)

Application
The interlocking for transformer bay (AB_TRAFO, 3) function is used for a
transformer bay connected to a double busbar arrangement according to figure 140.
The function is used when there is no disconnector between circuit breaker and
transformer. Otherwise, the interlocking for line bay (ABC_LINE, 3) function can be
used. This function can also be used in single busbar arrangements.
Section 14
Control
IP14149-1 v2
M13567-3 v7
383

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents