Testing The Gas Medium Supervision For Pressure Alarm And Pressure Lockout Conditions; Testing The Gas Medium Supervision For Temperature Alarm And Temperature Lock Out Conditions; Completing The Test; Liquid Medium Supervision Ssiml - ABB Relion 670 Series Commissioning Manual

Bay control version 2.2 iec
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
Check that the input logical signal BLOCK is logical zero and that on the local HMI, the logical
signals PRESALM, PRESLO, TEMPALM, TEMPLO, ALARM and LOCKOUT are logical zero.
Using service kit. prepare the IED for verification of settings as outlined in Section
the IED to verify settings"
11.12.1.1
Testing the gas medium supervision for pressure alarm and pressure
lockout conditions
1.
Connect binary inputs to consider gas pressure and gas density to initiate the alarms.
2.
Consider the analogue pressure input SENPRES and set SENPRES to a value lower than
PresAlmLimit or activate binary input signal SENPRESALM, check that outputs PRESALM
and ALARM are activated after a set time delay of
3.
Gas pressure lockout input SETPLO can be used to set PRESLO.
4.
Also, reduce further the pressure level input below
input signal SENPRESLO, check that PRESLO signal appears after a set time delay of
tPressureLO .
5.
Activate BLOCK binary input and check that the outputs PRESALM, PRESLO, ALARM and
LOCKOUT disappear.
6.
Reset the BLOCK binary input.
7.
Make sure that pressure lockout condition exists and then activate the reset lock out
input RESETLO and check that the outputs PRESLO and LOCKOUT reset.
11.12.1.2
Testing the gas medium supervision for temperature alarm and
temperature lock out conditions
1.
Consider the analogue temperature input SENTEMP and set SENTEMP to a value higher
than
time delay of
2.
Temperature lockout input SETTLO can be used to set TEMPLO signal.
3.
Also, increase further the temperature input above
TEMPLO and LOCKOUT appears after a set time delay of
4.
Activate BLOCK binary input and check that the outputs TEMPALM, TEMPLO, ALARM and
LOCKOUT disappear.
5.
Reset the BLOCK binary input.
6.
Make sure that temperature lockout condition exists and then activate the reset lock out
input RESETLO and check that the outputs TEMPLO and LOCKOUT reset.
11.12.1.3

Completing the test

Continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
11.12.2

Liquid medium supervision SSIML

Prepare the IED for verification of settings as outlined in section
settings"
Values of logical signals for SSIMG protection are available on the local HMI under Main menu/
Tests/Function status/Monitoring/InsulationLiquid(71)/SSIML(71):x, where x = 1, 2,....4.
Check that the input logical signal BLOCK is logical zero and that on the local HMI, the logical
signals LVLALM, LVLLO, TEMPALM, TEMPLO, ALARM and LOCKOUT are logical zero.
174
in this chapter.
TempAlarmLimit , check that outputs TEMPALM and ALARM are activated after a set
tTempAlarm .
in this chapter.
© Copyright 2017 ABB. All rights reserved
GUID-768DAAC8-F89D-4401-B86D-9B26FD7224F6 v3
tPressureAlarm .
PresLOLimit or activate the binary
GUID-EC145626-90B0-45A2-AD58-CB8BF203FE16 v1
TempLOLimit , check that the outputs
tTempLockOut .
GUID-DD08C598-A35C-4300-9555-A0877F7DC511 v2
TestMode setting to Off .
GUID-6426FDDA-B949-4FE7-BF42-B52014A9344B v4
"Preparing the IED to verify
Commissioning manual
1MRK 511 403-UEN E
"Preparing
Bay control REC670

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents