Setting The Tcp/Udp Client Communication - ABB Relion 670 Series Commissioning Manual

Bay control version 2.2 iec
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
PMUCONF. The first three parameters are related to TCP communication. The default
TCP parameters setting can be used. More information regarding TCP communication is
available in the Application manual under section Short guidance for use of TCP.
3.
Set the UDP communication parameters by navigating to: Main menu/Configuration/
Communication/Station communication/phasor measurement/PMU Configuration/
PMUCONF. The first three parameters are related to TCP communication and the rest of
parameters are related to setting of six independent UDP client groups. Each UDP group
has eight parameters. More information regarding UDP communication is available in the
Application manual under section Short guidance for use of UDP. The following steps
describes setting parameters for the first UDP group:
3.1.
3.2.
3.3.
9.4

Setting the TCP/UDP client communication

As an example of a TCP/UDP client, the openPDC tool (PMU Connection Tester Ver. 4.2.12)
from Grid Protection Alliance is used in this section. Install PMU Connection Tester tool on a PC
with Ethernet network adaptor available. The same PC used for PCM600 can be used to install
the PMU Connection Tester tool.
IEC140000133 V1 EN-US
Figure 9:
The following steps explain how to set the PMU Connection Tester parameters in order to
establish an IEEE C37.118 connection with the PMU:
1.
Set the IP stack on PMU Connection Tester to IPv4. Note that the default IP stack on PMU
Connection Tester tool is IPv6.
68
Enable the first UDP group by setting the parameter
Set the UDP client IP address by setting the parameter
192.168.1.99. For the purpose of the communication set-up in this section the LAN
IP address of the PC is used, where the PDC client tool is installed.
The default parameter settings can be used for the rest of parameters for the first
UDP group.
PMU Connection Tester tool
© Copyright 2017 ABB. All rights reserved
1MRK 511 403-UEN E
SendDataUDP1 to On .
UDPDestAddres1 to
GUID-6CEE3261-D211-4051-8CA8-5840C27C560E v2
IEC140000133-1-en.vsd
Bay control REC670
Commissioning manual