ABB Relion 670 Series Commissioning Manual page 75

Bay control version 2.2 iec
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 403-UEN E
IEC140000134 V1 EN-US
1.1.
1.2.
2.
Set the Connection Parameters on PMU Connection Tester for TCP communication
according to the PMU configuration.
IEC140000135 V1 EN-US
2.1.
2.2.
2.3.
2.4. Set the
Bay control REC670
Commissioning manual
Navigate to the Settings tab.
Force the IP stack to IPv4 by setting the parameter
Host IP to the PMU IP address configured for the port in use. Here the LANAB:1
Set
IPAddress (192.168.1.10) is set.
Port to the IED's TCP port set in the PMU under parameter C37.118TCPport
Set
(4712 is default). Alternatively, in order to make an IEEE1344 communication, the
1344TCPport parameter setting can be used (4713 is default).
Set the Protocol as IEEE C37.118.2-2011.
Device ID Code in PMU Connection Tester per PMU Data Stream ID Number
(IDCODE). The PMU Data Stream ID Number is a user assigned ID number (1-65534)
for each data stream sent out from the PMU and it is defined under parameter
© Copyright 2017 ABB. All rights reserved
Establishing connection and verifying the IEEE C37.118/1344 communication
IEC140000134-1-en.vsd
ForceIPv4 to True .
IEC140000135-1-en.vsd
Section 9
69