Measuring The Operate And Time Limit For Set Values - ABB Relion 670 Series Commissioning Manual

Bay control version 2.2 iec
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 403-UEN E
11.4.6.1

Measuring the operate and time limit for set values

Operation mode 3I
Procedure
1.
Set the polarizing voltage to 1.2 ·
current to the set characteristic angle (
voltage.
Take setting
2.
Inject current until the function picks up, and make sure that the operate current of the
set directional element is equal to the
The I Dir (3I
3.
Assume that φ´ is the phase angle between injected voltage (3U
´ =
the function operates.
4.
Compare the result with the set value and make sure that the new injected 3I
equal to the setting
Take the set characteristic into consideration, see Figure
5.
Measure the operate time of the timer by injecting a current two times the set
value and the polarizing voltage 1.2 ·
Tinv
IECEQUATION2402 V2 EN-US
6.
Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7.
Set the polarizing voltage to zero and increase until the boolean output signal UNREL is
activated, which is visible in the Application Configuration in PCM600 when the IED is in
online mode. Compare the voltage with the set value
8.
Continue to test another function or complete the test by setting the test mode to
Bay control REC670
Commissioning manual
· cosφ
0
RCAComp into consideration if not equal to 0 .
· cosφ) function activates the START and STDIRIN output.
0
RCADir -φ. Change φ´ to for example 45 degrees. Increase the injected current until
INcosPhi> ..
×
kSN Sref
=
( )
×
×
3
I
3
U
j
cos
0
test
0
test
© Copyright 2017 ABB. All rights reserved
UNRel> and set the phase angle between voltage and
RCADir ). Note that the the current lagging the
INcosPhi> setting.
UNRel> .
UNRel> .
Testing functionality by secondary injection
) and current (3I
0
· cos φ is
0
24
and Figure 25.
INcosPhi>
(Equation 1)
Section 11
SEMOD175060-12 v2
SEMOD175060-34 v9
) i.e. φ
0
Off .
99