1MRK 511 403-UEN E
11.17
Exit test mode
The following procedure is used to return to normal operation.
1.
Navigate to the test mode folder.
2.
Change the
3.
Answer
Bay control REC670
Commissioning manual
After exiting the IED test mode, make sure that the MU is returned to normal
mode.
On setting to Off . Press the 'E' key and the left arrow key.
YES , press the 'E' key and exit the menus.
© Copyright 2017 ABB. All rights reserved
Testing functionality by secondary injection
Section 11
SEMOD53244-3 v6
187