Completing The Test; Rate-Of-Change Frequency Protection Sapfrc; Verifying The Settings; Frequency Time Accumulation Protection Function Ftaqfvr - ABB Relion 670 Series Commissioning Manual

Bay control version 2.2 iec
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
5.
Slowly increase the frequency of the applied voltage, to a value above
6.
Check that the START signal does not appear.
7.
Wait for a time corresponding to
11.6.2.2

Completing the test

continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
11.6.3

Rate-of-change frequency protection SAPFRC

Prepare the IED for verification of settings as outlined in section
section
11.6.3.1

Verifying the settings

Verification of START value and time delay to operate
1.
Check that the settings in the IED are appropriate, especially the START value and the
definite time delay. Set
2.
Supply the IED with three-phase voltages at their rated values.
3.
Slowly decrease the frequency of the applied voltage, with an increasing rate-of-change
that finally exceeds the setting of
appears.
4.
Note the operate value and compare it with the set value.
5.
Increase the frequency to rated operating conditions, and zero rate-of-change.
6.
Check that the START signal resets.
7.
Instantaneously decrease the frequency of the applied voltage to a value about 20%
lower than the nominal value.
8.
Measure the time delay for the TRIP signal, and compare it with the set value.
Extended testing
1.
The test above can be repeated to check a positive setting of
2.
The tests above can be repeated to check the time to reset.
3.
The tests above can be repeated to test the RESTORE signal, when the frequency
recovers from a low value.
11.6.3.2
Completing the test
continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
11.6.4

Frequency time accumulation protection function FTAQFVR

Prepare the IED for verification of settings as outlined in section "Overview" and section
"Preparing for test" in this chapter.
130
"Preparing for test"
in this chapter.
StartFreqGrad , to a rather small negative value.
© Copyright 2017 ABB. All rights reserved
tDelay , make sure that the TRIP signal does not appear.
StartFreqGrad , and check that the START signal
1MRK 511 403-UEN E
StartFrequency .
TESTMODE setting to Off .
"Requirements"
and
StartFreqGrad .
TESTMODE setting to Off .
GUID-F7BD8E10-EF88-4698-87F4-0D4365004705 v2
Bay control REC670
Commissioning manual
M16290-52 v5
M16256-2 v6
M16256-8 v1
M16256-10 v5