ABB Relion 670 Series Commissioning Manual page 76

Bay control version 2.2 iec
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
2.5.
2.6. Continue to the section
3.
Set the Connection Parameters on PMU Connection Tester for UDP communication
according to the PMU configuration.
IEC140000136 V1 EN-US
3.1.
3.2.
3.3.
3.4. Set the
3.5.
3.6. Continue to the section
70
PMUdataStreamIDCODE . (Main menu/Configuration/Communication/Station
communication/phasor measurement/PMU Report/PMUREPORT:1)
Configure Alternate Command Channel is set as Not Defined .
Make sure that the
Configure Alternate Command Channel is used to configure a TCP channel to
The
control the UDP data communication and transfer the header, configuration and
command frames.
Local Port to UDP destination port defined in the PMU under the parameter
Set the
UDPDestPort1 (Default value: 8910).
Click the Configure Alternate Command Channel to configure the TCP channel. A
new window will pop up. A TCP channel needs to be configured in order to control
the UDP data communicatiuon and transfer the header, configuration and
command frames.
IEC140000137 V1 EN-US
Host IP as the PMU IP address configured for the port in use. Here the
Set the
LANAB:1 IPAddress (192.168.1.10) is set.
Port as the TCP port defined in the PMU for control of data sent over UDP
client group 1 (Default value: 4713). This can be found under the parameter
TCPportUDPdataCtrl1 as one of the UDP communication parameters.
Save the Alternate Command Channel Configuration settings.
© Copyright 2017 ABB. All rights reserved
Verifying the IEEE C37.118/1344 TCP
Verifying the IEEE C37.118/1344 UDP communication
1MRK 511 403-UEN E
communication.
IEC140000136-1-en.vsd
IEC140000137-1-en.vsd
Bay control REC670
Commissioning manual