Fujitsu ETERNUS DX60 S4 Configuration Manual page 46

Hybrid storage systems / disk storage systems / all-flash arrays, eternus dx s4 series, eternus dx s3 series. eternus af series
Hide thumbs Also See for ETERNUS DX60 S4:
Table of Contents

Advertisement

Chapter 4 Connection and Settings
4.1 Setting the ETERNUS DX/AF
Auto Power
Select "Disable".
Power Resume
Select "Disable".
Connection CM
Select the controllers (CM#0 and/or CM#1) of the ETERNUS DX60 S4/DX100 S4/DX200 S4, ETERNUS DX500
S4/DX600 S4, ETERNUS DX60 S3/DX100 S3/DX200 S3, ETERNUS DX500 S3/DX600 S3, ETERNUS AF250 S2/
AF650 S2, ETERNUS AF250/AF650, and ETERNUS DX200F that are connected to the power synchronized
unit with the RS232C cable.
Select "CM#0" when the power synchronized unit is connected to the PWC port on controller 0. Select
"CM#1" when the power synchronized unit is connected to the PWC port on controller 1.
When different power synchronized units are connected to controller 0 and controller 1 in a duplicated
configuration, select both "CM#0" and "CM#1".
Delay until Shutdown
Do not change the default setting (0 minute).
Set management unit interface
Select "Power Synchronized Unit".
Power Failure Signal
"Positive" (positive logic) is automatically set.
Low Battery Signal
"Negative" (negative logic) is automatically set.
UPS Shutdown Signal
Do not select the "Enable" checkbox.
"Positive" (positive logic) is set by default.
FUJITSU Storage ETERNUS DX, ETERNUS AF Configuration Guide (Power Synchronized Unit)
46
Copyright 2017 FUJITSU LIMITED
P3AM-8012-10ENZ0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents