Configure Analog Services; Configure Telephony - ABB ETL600 Instruction Manual

Digital power line carrier system
Table of Contents

Advertisement

ABB Switzerland Ltd
In the frame Command outputs during link failure it can be
chosen how the command outputs should respond in case of a
level or SNR alarm of the NSD600 concerned (TPE link alarm).
Additionally a Pick up time (after the alarm condition has been
detected) and a Hold time (after the alarm condition has
disappeared) can be configured.
The Guard level alarm settings are valid for the corresponding
TPE only (they are different and independent from the settings
made under Configuration / System / Alarm settings for the
alarm threshold of the pilot levels; even if the NSD600 uses the
ETL-pilot as guard signal).
Note:
Remark for the tabs G4AI N11, ..., G4AI N71:
The various NSD600 signals (commands, alarms, acknowledges,
etc.) can be mapped to the designated Inputs and Outputs on
these tabs. It is noted that - for a certain G4AI - the configurable
signals are all from the same TPE.
The selections made in the frame Jumper settings for each input
port (Nominal input voltage or Contact only) and for each relay
output (Relay contact NO/NC) are for information purpose only;
the corresponding jumpers must be set on the interface modules
G4AI.
5.3.4.

Configure Analog Services

5.3.4.1.

Configure telephony

Point to Configuration / Telephony to get a dialog box with tabs CH1,
Slot N..., and/or CH2, Slot N..., and/or CH3, Slot N..., depending on
the required telephony services entered previously under Configure
services.
5-18
1KHW001489-EN
If the radio button Rx Output Duration is activated
on tab TPE1 or TPE2, the following settings in the
frame Command outputs during link failure are
not possible:
- direct to guard state, others to command state
- freezing of commands.
Vice versa, if one of the two settings mentioned
above is chosen, Rx Output Duration on tab TPE1
or TPE2 is not configurable.
If freezing of commands is chosen, Pick up time
and Hold time can not be varied (set to 0 s).
November 2005
ETL600
Configuration and Set-up

Hide quick links:

Advertisement

Table of Contents
loading