Instruction for Changing the Input Voltage of B5LC
Responsible Department:
Prepared:
PTUKT
1998-01-23 sig. R. Pauli
Valid for:
Derived from:
-
-
Power Line Carrier Equipment: Series ETL500/ETL600
Instruction for Changing the Input Voltage of B5LC
Contents
1
Purpose of document...................................................................................... 1
2
Safety instructions .......................................................................................... 1
3
Changing from 230 VAC to 115 VAC ............................................................. 2
4
Changing from 115 VAC to 230 VAC ............................................................. 2
1
Purpose of document
This document describes how to change the input voltage of the AC power supply type B5LC from
230 VAC to 115 VAC or vice versa.
2
Safety instructions
DANGER
Caution
Caution
Caution
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. © ABB Switzerland Ltd
ABB Switzerland Ltd
Approved:
1998-01-29 sig. T. Ruckli
Replaces:
-
Hazardous voltage and hazardous energy level.
Beware of electric shock.
Unplug the cables to the module from the mains before opening.
Follow the instruction below carefully and do not modify anything.
Wrong programming can damage the module and the equipment.
Check if programmed input voltage of the module is equal to the mains
voltage.
Verify the programming information on the right side of the module.
Operate the module only in the condition specified by the manufacturer.
1KHL015788-EN
Archive No.:
-
Distribution:
-
Classification-No.:
File:
-
1KHL015788ae Instruction for
changing the input voltage of
B5LC.doc
Rev.
Date:
A
2005-09-30
Lang.:
Page:
EN
1/2