ABB ETL600 Instruction Manual page 363

Digital power line carrier system
Table of Contents

Advertisement

Revision:
A
14. The Testconfiguration time dialog box has been opened by the HMI600.
Click OK.
15. The HMI600 now compares the equipment identification from the file with the identification
stored in the equipment. If it is different, a warning message box appears.
Click OK. This starts the download configuration process.
16. A dialog box informs you, that the configuration has not been stored in the non-volatile flash
EPROM and asks you if you want to do so.
Click Yes.
The configuration data are now stored in the flash EPROMs. This process needs some
seconds. Please wait until the color of the stop button in the toolbar changes from red to grey.
The actual status of the process is displayed in the status bar.
3.2
Update of already configured equipment
1.
On the File menu click New. This opens the Connect dialog box.
2.
Click Logon, Equipment ID: 0
3.
Click Read & Write access.
4.
Click Upload configuration.
5.
Click OK. This opens a HMI600 child window
6.
On the Equipment menu, click Commissioning and maintenance and then click Firmware
download...
7.
In the following message box click Yes if you are aware of a malfunction of the PLC link. This
opens the Firmware download dialog box. Otherwise click No.
8.
The checkbox Automatic firmware download has to be checked.
9.
Click Start firmware download to start the operation.
10. The following message box informs you which download files are used. Be sure that all files
are from the same release directory.
Click Yes to accept these files. This starts the firmware download. The HMI600 automatically
performs the update and resets the system after the update is completed.
Click No to select other files. This opens a file open dialog box for each kind of download file.
Click Cancel to stop firmware download.
11. Wait until the Close button changes to the active state.
12. Click Close to leave the firmware download dialog box.
3.3
Modify equipment if the configuration download detects an incompatibility
The HMI600 configuration download detects an incompatible firmware in the equipment and call for
a firmware download.
1.
You are informed of the incompatibility and in some cases the HMI600 modifies the
configuration and notifies you about it.
2.
On the Equipment menu, click Commissioning and maintenance and then click Firmware
download...
3.
In the following message box click Yes if you are aware of a malfunction of the PLC link. This
opens the Firmware download dialog box. Otherwise click No.
4.
The checkbox Automatic firmware download has to be checked.
5.
Click Start firmware download to start the operation.
6.
The following message box informs you which download files are used. Be sure that all files
are from the same release directory.
Click Yes to accept these files. This starts the firmware download. The HMI600 automatically
performs the update and resets the system after the update is completed.
Language: