1MRK 511 419-UUS A
650 series 2.2 ANSI
Point list manual
3.1 BINARY INPUTS
Capabilities
Static (Steady-State)
(leave tick-boxes blank if
Group Number: 1 Event
this data type is not
Group Number: 2
supported)
3.1.1 Static Variation reported when variation 0 requested or in response to Class polls:
● Variation 1 – packed
format
● Variation 2 – with flag
○ Based on point Index
(add column to table in
part 5)
3.1.2 Event Variation reported when variation 0 requested or in response to Class polls: Note: The
support for binary input events can be determined remotely using protocol object Group 0 Variation 237.
● Variation 1 – without
time
● Variation 2 – with
absolute time
● Variation 2 – with
relative time
○ Based on point Index
(add column to table in
part 5)
3.1.3 Event reporting mode: When responding with event data and more than one event has occurred for
a data point, an Outstation may include all events or only the most recent event. "All events" must be
checked to be compliant.
○ Only most recent
● All events
3.1.4 Binary Inputs included in Class 0 response:
● Always
○ Never
○ Only if the point is
assigned to a class
○ Based on point Index
(add column to table in
part 5)
3.1.5 Binary Inputs Event Buffer Organization: When event buffers are allocated per object group (see
part 1.7.6), indicate the number of events that can be buffered for Binary Inputs. If event buffers are not
allocated per object group then set "Fixed at 0".
● Fixed at 1000
○ Configurable, range
_______ to _______
○ Configurable,
selectable from
____,____,____
○ Configurable, other,
describe:
DNP3 protocol implementation
Current Value
If configurable, list
methods
One
PST or LHMI
(Obj1DefVar)
Three
PST or LHMI
(Obj2DefVar)
All events
Always
Section 3
51