ABB REB650 Manual page 61

Relion dnp, 650 series version 2.2
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 511 419-UUS A
650 series 2.2 ANSI
Point list manual
3.7 BINARY OUTPUTS
Capabilities
AND BINARY OUTPUT
(leave tick-boxes blank if
COMMANDS
this data type is not
Binary Outputs Group
supported)
Number: 10
Binary Output Events
Group Number: 11
Binary Output
Commands Group
Number: 12
Binary Output Command
Events Group Number:
13
○ Variation 1 –
command status
without time
○ Variation 2 –
command status with
time
○ Based on point Index
(add column to table in
part 5)
3.7.8 Event reporting mode: When responding with event data and more than one event has occurred for
a data point, an Outstation may include all events or only the most recent event
○ Only most recent
● All events
3.7.9 Command Event reporting mode: When responding with event data and more than one event has
occurred for a data point, an Outstation may include all events or only the most recent event
○ Only most recent
○ All events
3.7.10 Maximum Time between Select and Operate:
○ Not Applicable
○ Fixed at _____
seconds
● Configurable, range 1
to 60 seconds
○ Configurable,
selectable
from___,___,___
seconds
○ Configurable, other,
describe:
○ Variable, explain:
○ Based on point Index
(add column to table in
part 5)
3.7.11 Binary Outputs Event Buffer Organization: When event buffers are allocated per object group (see
part 1.7.6), indicate the number of events that can be buffered for Binary Outputs. If event buffers are not
allocated per object group then set "Fixed at 0".
Table continues on next page
DNP3 protocol implementation
Current Value
If configurable, list
methods
Not Supported
Not Supported
30 seconds
PST or LHMI
(tSelectTimeout)
Section 3
55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650Dnp3Red650Req650Ret650Dnp 670 series