ABB REB650 Manual page 68

Relion dnp, 650 series version 2.2
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

Section 3
DNP3 protocol implementation
62
3.9 ANALOG INPUTS
Capabilities
Static (Steady-State)
(leave tick-boxes blank if
Group Number: 30
this data type is not
Static Frozen Group
supported)
Number: 31
Event Group Number: 32
Frozen Analog Input
Event Group Number: 33
Deadband Group
Number: 34
● Variation 1 – 32-bit
without time
● Variation 2 – 16-bit
without time
● Variation 3 – 32-bit
with time
● Variation 4 – 16-bit
with time
● Variation 5 – single-
precision floating point
w/o time
● Variation 6 – double-
precision floating point
w/o time
● Variation 7 – single-
precision floating point
with time
● Variation 8 – double-
precision floating point
with time
○ Based on point Index
(add column to table in
part 5)
3.9.3 Event reporting mode: When responding with event data and more than one event has occurred for
a data point, an Outstation may include all events or only the most recent event. Only the most recent
event is typically reported for Analog Inputs. When reporting "only most recent", the analog value reported
in the response may be the value at the time of the original event or it may be the value at the time of the
response.
● A: Only most recent
(value at time of event)
● B: Only most recent
(value at time of
response)
● C: All events
○ Based on point Index
(add column to table in
part 5)
3.9.4 Analog Inputs Included in Class 0 response:
Table continues on next page
Current Value
If configurable, list
methods
One
PST or LHMI
(Obj32DefVar)
Most Recent – Event
Time
1MRK 511 419-UUS A
650 series 2.2 ANSI
Point list manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650Dnp3Red650Req650Ret650Dnp 670 series

Table of Contents