1MRK 511 419-UUS A
650 series 2.2 ANSI
Point list manual
3.9 ANALOG INPUTS
Capabilities
Static (Steady-State)
(leave tick-boxes blank if
Group Number: 30
this data type is not
Static Frozen Group
supported)
Number: 31
Event Group Number: 32
Frozen Analog Input
Event Group Number: 33
Deadband Group
Number: 34
3.9.1 Static Variation reported when variation 0 requested or in response to Class polls:
● Variation 1 – 32-bit
with flag
● Variation 2 – 16-bit
with flag
● Variation 3 – 32-bit
without flag
● Variation 4 – 16-bit
without flag
● Variation 5 – single-
precision floating point
with flag
● Variation 6 – double-
precision floating point
with flag
○ Based on point Index
(add column to table in
part 5)
3.9.2 Event Variation reported when variation 0 requested or in response to Class polls: Note: The
support for analog input events can be determined remotely using protocol object Group 0 Variation 231.
Table continues on next page
DNP3 protocol implementation
Current Value
If configurable, list
methods
Three
PST or LHMI
(Obj30DefVar)