Section 5
Mounting
5.3.2
5.3.2.1
24
PosNo
Description
1
Sealing strip, used to obtain
IP54 class. The sealing strip is
factory mounted between the
case and front plate.
2
Fastener
3
Groove
4
Screw
5
Joining point of sealing strip
6
Panel

19" panel rack mounting

Overview

All IED sizes can be mounted in a standard 19" cubicle rack by using a suitably
sized mounting kit consisting of two mounting angles, their fastening screws and
washers.
The mounting angles are reversible which enables mounting of IED size 1/2 x 19"
or 3/4 x 19" either to the left or the right side of the cubicle.
A separately ordered rack mounting kit for side-by-side mounted
IEDs or IEDs together with RHGS cases should be selected so that
the total size equals 19".
Use only the screws included in the mounting kit when mounting
the plates and the angles on the IED. Screws with wrong dimension
may damage the PCBs inside the IED.
1MRK 514 026-UEN B
Quantity
Type
-
-
2
-
-
-
4
M3x8 mm
-
-
-
-
670 series 2.2 IEC
Installation manual
IP10313-1 v1
SEMOD127656-5 v4