Section 6
Connecting
70
IED
VOLTAGE MEASURE (U)
CURRENT MEASURE (U)
VOLTAGE MEASURE (U)
CURRENT MEASURE (U)
IEC11000209 V1 EN-US
Figure 42:
Separate analog inputs for stator STTIPHIZ and rotor
ROTIPHIZ protection
2.
It is possible to use a mixed connection that requires only two IED voltage
channels for both ROTIPHIZ and STTIPHIZ. REX060 outputs are connected
in series. This connection is not recommended and can be used only in
applications where it is prove the possibility to use it. the use of this
connection leads to reduced performances of both ROTIPHIZ and STTIPHIZ.
IED
VOLTAGE MEASURE (U)
CURRENT MEASURE (U)
IEC11000210 V1 EN-US
Figure 43:
Connection to IED with two analogue voltage inputs
1MRK 514 026-UEN B
REX060
X61
8
9
STATOR MODULE SIM
10
11
X81
8
9
ROTOR MODULE RIM
10
11
IEC11000209-1-en.vsd
REX060
X61
8
9
STATOR MODULE SIM
10
11
X81
8
9
ROTOR MODULE RIM
10
11
IEC11000210-1-en.vsd
670 series 2.2 IEC
Installation manual