Mounting procedure for side-by-side rack mounting

3
4
IEC04000456 V3 EN-US
Figure 7:
Side-by-side rack mounting details.
The required torque for the screws is 3.5 Nm.
PosNo
Description
1
Mounting plate
2, 3
Screw
4
Mounting angle
5
Washer

IED mounted with a RHGS6 case

A 1/2 x 19" or 3/4 x 19" size IED can be mounted with a RHGS case (6 or 12
depending on IED size). The RHGS case can be used for mounting a test switch of
type RTXP 24. It also has enough space for a terminal base of RX 2 type for
mounting of, for example, a DC-switch or two auxiliary relays.