Wall Mounting; Overview - ABB RELION 670 Series Installation Manual

Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 5
Mounting
5.3.3
5.3.3.1
26
PosNo
Description
1a, 1b
Mounting angles, can be mounted
either to the left or the right side of
the case
2
Screw
3
Washer

Wall mounting

Overview

All case sizes, 1/2 x 19", 3/4 x 19",1/1 x 19", can be wall mounted. It is also
possible to mount the IED on a panel or in a cubicle.
Use only the screws included in the mounting kit when mounting
the plates and the angles on the IED. Screws with wrong dimension
may damage the PCBs inside the IED.
If fiber cables are bent too much, the signal can be weakened. Wall
mounting is therefore not recommended for any communication
modules with fiber connection.
1MRK 514 026-UEN B
Quantity
Type
2
-
8
M4x6
8
M4x6
670 series 2.2 IEC