REX062 Shunt resistor unit connections
Table 18:
Injection via shunt resistors connection X1
No
1
-
2
Injection
3
-
4
Injection return
5
-
6
Current sense output
7
-
8
Current sense output
9
Injection input, External shunt
10
Injection input return, External shunt
X1 connector. Connect each signal connector terminal of screw compression type
2
with one 0.14 to 6 mm
(AWG 35 - AWG 15) wires.
Protective conductor terminal must be connected to the cubicle or station protective
earthing system. Electrical codes and standards require that protective earth cables
are green/yellow conductors with a cross section area of at least 2.5 mm
14). The cubicle must be properly connected to the station earthing system. Use a
conductor with a core cross section area of at least 4 mm

Connecting and setting voltage inputs

The RIM module of REX060 has two analog output channels that shall be
connected to two voltage input channels of the IED.
If both stator and rotor protection are used, there are two possible methods to
perform the connection.
1.
The recommended connection require four analog channels of the IED: two
IED voltage channels are used for the measured quantities for ROTIPHIZ; two
more IED voltage channels are used for the measured quantities for
STTIPHIZ.
Signal
(AWG 35 - AWG 3) wire or with two 0.14 to 1.5 mm
Section 6
Connecting
2
2
(AWG
2
(AWG 12).
GUID-BE3E0554-3E96-4489-B8C9-E62953853BB7 v4