ABB COM600S User Manual page 31

Com600 series, modbus tcp master, opc
Hide thumbs Also See for COM600S:
Table of Contents

Advertisement

1MRS756445
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Property/Para-
Value or Value range/ Default
meter
/Example
Subtype
REGISTERED_BASE_CON-
TROL
Addresses
Format
Float MSW first
Float MSW last
Default: Float MSW first
Set Point Register
0 to 65535
Default: 0
Table 3.4.8.3-2 Configurable ACP properties for OPC servers with Modbus IED,
subtype DPU_REGISTERED_BASE
Property/Para-
Value or Value range/ Default
meter
/Example
Basic
61850-Type
APC
Subtype
DPU_REGISTERED_BASE_CON-
TROL
Addresses
Format
Float MSW first
Float MSW last
Default: Float MSW first
Set Point Register
0 to 65535
Default: 0
Execute Register
0 to 65535
Address for pass-
0 to 65535
word 1
Address for pass-
0 to 65535
word 2
Description
Data format for the value.
Holding register address for the set point.
Holding register (4X reference) address
range 40001 to 49999. Address 0 equals
to no information available.
Description
61850-Type
Data format for the value.
Holding register address for the set point.
Holding register (4X reference) address
range 40001 to 49999. Address 0 equals
to no information available.
6x extended register. Extended register
(6x reference) address range 60001 to
65535. Address 0 equals to no information
available(0 to 65535)
ASCII – 2 Characters Leftmost Digits 6x
extended register. Extended register (6x
reference) address range 60001 to 65535.
Address 0 equals to no information avail-
able(0 to 65535)
ASCII – 2 Characters rightmost Digits 6x
extended register. Extended register (6x
reference) address range 60001 to 65535.
Address 0 equals to no information avail-
able(0 to 65535)