1MRS756445
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Property/Para-
Value or Value range/ Default
meter
/Example
Bit Mask for Fail
0 - 65535
Alarm
Default 0
Bit Mask for Inverse
0 - 65535
status
Default 0
Bit Mask For Inter-
0 - 65535
mediate Status
Default: 0
Bit Mask For Status
0 - 65535
Default: 0
Close Indication
0 - 65535
Coil/Input
Default: 0
Fail Alarm register
0 - 65535
Default 0
Fail Indication
0 - 65535
Coil/Input
Default: 0
Indication Register
0 - 65535
Default 0
Inverse status
0 - 65535
register
Open indication
0 - 65535
Coil/Input
Default: 0
Description
Bit mask for fail alarm
Bit mask for inverse status
Bit mask for intermediate status.
Bit mask for status.
Coil or input address for the close indica-
tion. Coil (0X reference) address range 1
- 9999 or input (1X reference) address
range 10001 - 19999 . Address 0 equals
to no information available.
Holding address for the Fail alarm. Holding
register = 4x reference address range
40001 - 49999 .
Address 0 equals to no information avail-
able.
Coil or input address for the fail indication
(optional). Coil (0X reference) address
range 1 - 9999 or input (1X reference)
address range 10001 - 19999 . Address
0 equals to no information available.
Holding address for the Fail alarm. Holding
register = 4x reference address range
40001 - 49999 .
Address 0 equals to no information avail-
able.
Holding address for the Fail alarm. Holding
register = 4x reference address range
40001 - 49999 .
Address 0 equals to no information avail-
able.
Coil or input address for the open indica-
tion. Coil (0X reference) address range 1
- 9999 or input (1X reference) address
range 10001 - 19999 . Address 0 equals
to no information available.
53