Double Point Status (Dps) - ABB COM600S User Manual

Com600 series, modbus tcp master, opc
Hide thumbs Also See for COM600S:
Table of Contents

Advertisement

3.4.8.10.
52
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Property/Para-
Value or Value range/ Default
meter
/Example
Leftmost register for
40001 - 49999
Vendor location
Rightmost register
40001 - 49999
for Vendor location
Indication scale
Lookup table scale
Stepwise Linear scale
Default: NONE

Double point status (DPS)

Double Point Status (DPS) for OPC server with Modbus IED supports the following
subtypes:
BIT
BIT_IN_REGISTER_WITH_INTERMEDIATE_BIT
BIT_DPU
BIT_DPU_MCD
BIT_DPU_INREGISTER
Table 3.4.8.10-1 Configurable DPS properties for OPC servers with Modbus device,
subtype BIT, BIT_IN_REGISTER_WITH_INTERMEDIATE_BIT, BIT_DPU,
BIT_DPU_MCD
Property/Para-
Value or Value range/ Default
meter
/Example
Basic
61850-Type
DPS
Subtype
BIT
BIT_DPU
BIT_DPU_MCD
BIT_IN_REGISTER_WITH_INTER-
MEDIATE_BIT
BIT_DPU_INREGISTER
Addresses
Address For Status
0 - 65535
and Intermediate
Default: 0
Description
Holding address for the Serial number.
Holding register = 4x reference address
range 40001 - 49999 . Address 0 equals
to no information available.
Holding address for the Serial number.
Holding register = 4x reference address
range 40001 - 49999 . Address 0 equals
to no information available.
Scale to be used with the indication value
Description
61850-Type
Address for status and intermediate.
1MRS756445

Advertisement

Table of Contents
loading