Property/Para-
Value or Value range/ Default
meter
Sub Type
Addresses
Control Coil
0...65535
Indication Coil/Input
0...65535
OPC Alarm and
Event
Control Event Class
Default: 0
Indication Event
Default: None
Class

Single point status (SPS)

Table 3.4.7.4-1 Configurable SPS (for OPC internal data) properties for OPC servers
Property/Para-
Value or Value range/ Default
meter
Basic
Common Data
SPS
Class
Addresses
Item Tag Path
Alarm and Event
Indication Event
Default: Empty string
Description
Sub type of object
Coil address for the control. Coil (0X refer-
ence) address range 1...9999. Address 0
equals to no information available.
Coil or input address for the indication.
Coil = 0X reference address range
1...9999 or input = 1X reference address
range 10001...19999. Address 0 equals
to no information available.
Event class to be used for the control
events.
Event class to be used for the indication
events.
Description
Common data class according to IEC
61850
Item tag path for the internal status
information. The internal server tags that
can be used are located in the Attributes
nodes that are located under the root, line,
and IED nodes. When an attribute tag is
referred to in the internal item definitions
below, it is possible to use either the whole
tag path or just the path relative to the IED
(the internal tags are configured per IED);
e.g. Attributes\Diagnostic counters\Trans-
mitted data messages. When the whole
path is used, it must be preceded by a
slash (/) character, e.g. /Channel
Name\Attributes\Diagnostic counters\Trans-
mitted data messages.
Indication event used with this data object.