3.4.8.17.
64
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Property/Para-
Value or Value range/ Default
meter
/Example
Address for Pass-
0 to 65535
word 1
Default: 0
Address for Pass-
0 to 65535
word 2
Default: 0
Password
Default: empty string.
Length: 4 characters

Single point status (SPS)

Single Point Status (SPS) for OPC server with Modbus IED supports the following
subtypes:
BIT
BIT_DPU_MCD
BIT_IN_REGISTER
Table 3.4.8.17-1 Configurable SPS properties for OPC servers with Modbus device,
subtype BIT AND BIT_IN_REGISTER
Property/Para-
Value or Value range/ Default
meter
/Example
Basic
61850-Type
SPS
Sub-Type
BIT
BIT_IN_REGISTER
Default: BIT
Addresses
Indication Coil/Input
0 to 65535
Default: 0
Description
Holding address for password 1. Holding
register = 4x reference address range
40001 to 49999.
Address 0 equals to no information avail-
able
Holding address for password 2. Holding
register = 4x reference address range
40001 to 49999.
Address 0 equals to no information avail-
able
IED device 4 character password. Default
is empty string.
Description
61850-Type
Sub type for SPS.
Coil or input address for the indication.
Coil (0X reference) address range 1 to
9999 or input (1X reference) address
range 10001 to 19999. Address 0 equals
to no information available.
1MRS756445