Configuring Data Objects - ABB COM600S User Manual

Com600 series, modbus tcp master, opc
Hide thumbs Also See for COM600S:
Table of Contents

Advertisement

1MRS756445
3.4.8.
3.4.8.1.
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual

Configuring data objects

Directional protection activation information
Table 3.4.8.1-1 Configurable ACD properties for OPC Servers with Modbus IED
Device
Property/Para-
Value or Value range/ Default
meter
/Example
Basic
61850-Type
ACD
Sub Type
BIT
Addresses
General Coil/Input
0 to 65535
Default: 0
Neutral Coil/Input
0 to 65535
Default: 0
Phase A Coil/Input
0 to 65535
Default: 0
Phase B Coil/Input
0 to 65535
Default: 0
Phase C Coil/Input
0 to 65535
Default: 0
Description
61850-Type
Sub type for the object
Coil or input address for General informa-
tion. Coil (0X reference) address range 1
to 9999 or input (1X reference) address
range 10001 to 19999. Address 0 equals
to no information available.
Coil or input address for Neutral informa-
tion. Coil (0X reference) address range 1
to 9999 or input (1X reference) address
range 10001 to 19999. Address 0 equals
to no information available.
Coil or input address for Phase A informa-
tion. Coil (0X reference) address range 1
to 9999 or input (1X reference) address
range 10001 to 19999. Address 0 equals
to no information available.
Coil or input address for Phase B informa-
tion. Coil (0X reference) address range 1
to 9999 or input (1X reference) address
range 10001 to 19999. Address 0 equals
to no information available.
Coil or input address for Phase C informa-
tion. Coil (0X reference) address range 1
to 9999 or input (1X reference) address
range 10001 to 19999. Address 0 equals
to no information available.