Configuring Modbus Tcp Device - ABB COM600S User Manual

Com600 series, modbus tcp master, opc
Hide thumbs Also See for COM600S:
Table of Contents

Advertisement

3.4.4.
24
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Property/Parameter
Polling Period

Configuring Modbus TCP Device

Table 3.4.4-1 lists the configurable properties for Modbus Devices and value ranges for
these properties. The actual configuration by using SAB600 is performed as described
in 3.4.1, General about configuring objects.
Table 3.4.4-1 Modbus TCP IED properties
Name
Value or Value range/ Default
Basic
Diagnostics enabled
True
False
Default: False
In Use
In use
Not in use
Default: In use
Maximum Topic
1..1000
Range
Default: 10
Simulation Mode
True
False
Default: False
Addresses
Internet Address
127.0.0.1
Station Address
0..255
Default: 1
Timeouts
Connection Timeout
0..3600
Default: 500
Value or Value range/ Default
0..255
Default: 3
Description
Diagnostics Enabled
Controls whether the device communica-
tions initially in use or not.
The maximum length of address between
first and last address index in one Topic.
Specifies whether the device is insimula-
tion mode or not.
Defines the internet address of this IED.
Port number can be configured by using
semicolon (GW 4.0 or newer). For
example, "127.0.0.1;8080".
Modbus address of the device.
Defines the timeout.
1MRS756445
Description
The polling frequency of sus-
pended stations.
1 = each polling cycle, 2 =
Every 2nd polling cycle, etc.