4.5.5 Digital Indicator View

Short Channel Tag
Level
Level
Current Value
Alarm Status
In Flow
Units
Temp
Recording
Chart
Bar
Process
On
Digital view enable
Totalizer display enable
Menu enables
Digital menu enables
1. Message select enable
2. Alarm acknowledge enable
3. Totalizer reset enable
4. Totalizer stop/go enable
5. Channel select enable
Group 1
2.08
2.08
metres
metres
578494
578494
3
m
3
m
204.4
l/hr
0005402801
3
m
195
°C
3
m
Digital
Archive
On
1 2 3 4 5
28/03/00
14:52:00
Pressure
4
2.08
metres
bar
578494
3
m
Out Flow
198.4
l/hr
0005402060
3
m
Alarm 1
On
Set to 'On' to enable the operator to display the Digital
Indicator view.
Note. This parameter is displayed only if the Totalizer option
is fitted.
Set to 'On' to add the channel totalizer value and units to the
indicator displays (if the totalizer for that channel is enabled).
Select the menu items to be accessible from the Digital
Indicator view.
Message select enable
Enables the Operator to activate one of 24 pre-configured
messages or a user-defined message.
Alarm acknowledge enable
Enables the Operator to acknowledge any alarms
associated with the current group.
Totalizer reset enable
Enables the Operator to reset the totalizer value to the preset
totalizer value on any or all channels.
Totalizer stop/go enable
Enables the Operator to start and stop the totalizer.
Channel select enable
Enables the Operator to display or hide individual channels.
Notes.
• Menu items that are not enabled are greyed-out in the
Digital Indicator view menu.
• Totalizer menu options can be enabled only if the Totalizer
option is fitted.
4 CONFIGURATION...
Channel Units
Totalizer Units
See Note below
Totalizer Value
Note. Displayed only if the
Totalizer option is fitted
enabled for that channel (see
Section 4.6.5)
for display
and
(see below).