...2 OPERATION

...2.3 Chart Views

Notes.
1. Current Values
The Current Value, shown on the digital indicators at either the top (vertical chart view) or right hand side (horizontal chart
view) of the screen, is the latest instantaneous value and its update rate is not affected by the recording sample rate.
If the current value in the digital indicator is displayed in red, recording has been stopped for that channel – see Sections 3.3
and 4.5.1.
Traces are shown only when that particular channel is being recorded. When a channel is set to stop, its trace continues
to be shown for up to one sample period.
2. Alarm Status
• Flashing red alarm event icon – alarm active and unacknowledged
• Continuous red alarm event icon – alarm active and acknowledged
If
alarm in
process group is active, the Global Alarm status icon (
any
any
Fig. 2.3. If
active alarm in
any
3. Alarm Event and Operator Message Annotations
Alarm Event and Operator Message annotations are not shown on the chart unless enabled – see 'Chart Annotation'
on page 8 and Section 4.5.2.
If Alarm event annotation is enabled and an alarm becomes active, a red alarm icon surrounded by a channel-colored box
is displayed at the point at which the alarm occured, together with the alarm time and tag, e.g.
11:58:00 1.1A High Level
If more than one alarm occurs in the same sample period:
• and the second alarm on a channel becomes active, its icon is added behind the first.
• and more than one operator message is active (max. six), a second icon is added behind the first.
• the new alarm event icons appear to the left of earlier icons.
• the time and tag of the oldest alarm (right-most icon) only is displayed.
Configuration
Setup
Historical Review
6
process group is unacknowledged, the icon is surrounded by a red flashing border.
any
Select the Configuration Level – see Section 4.
Select the Setup Level – see Section 3.
Select Historical Review to view previously recorded data stored in the instrument's
onboard memory.
Note. Use the
and
data.
Process Group 1
Level
Pressure
Digital
2.08
Indicators
metres
0
12:00:00
11:59:00
11:58:00
11:57:00
) is displayed in the status bar – see
keys to move backwards and forwards through the recorded
Historical
Invalid data – e.g.
Review Active
recording disabled
In Flow
Out Flow
Temp
4
204.9
198.9
- - - -
bar
l/hr
l/hr
11:58:23 Duty/Standby Pumps Switched
11:57:30 High Level
28/03/00
Values displayed
11:59:30
indicate the process
Alarm 1
status at the cursor
On
position
°C
10
Cursor