Mains Power Connections; Relay Output Board Connections; Hybrid I/O Module Connections; Digital Output Connections - ABB SM1000 User Manual

Inform it videographic recorder
Hide thumbs Also See for SM1000:
Table of Contents

Advertisement

5.6 Mains Power Connections – Fig 5.9
Fuse,
315mA, Type T
Line
Neutral
Terminal Block E
Warning. Use fuse rating – 315mA (max.) type T.
A – AC Supply
Fuse,
3A, Type T
+
24V DC
-
Terminal Block E
Warning. Use fuse rating – 3A (max.) type T.
B – DC Supply
Fig. 5.9 Mains Power Supply
5.7 Relay Output Board Connections – Fig. 5.10
Notes.
• The maximum total combined current flowing
through the relays is 36A. The maximum individual
relay current is 5A.
• The polarity is selected during I/O module
configuration – see Section 4.7.2.
17
14
11
18
15
12
19
16
13
Terminal Block C or D
Note. Relay contacts are fitted with arc suppression
components as standard.
Fig. 5.10 Relay Connections
1
L
85 min. to 265V max.
2
N
50/60Hz
3
4
5
6
7
8
1
2
3
4
5
6
7
8
7
4
1
NC
8
5
2
NO
9
6
3
C

5.8 Hybrid I/O Module Connections

5.8.1 Digital Output Connections – Fig 5.11
Six digital outputs are provided on the Hybrid option board.
do1
9
do2
10
do3
11
do4
12
do5
13
Digital Output
do6
14
15
COM
Common
COM
16
Note. Voltage level: 5V.
Load:
450Ω min.
Fig. 5.11 Digital Output Connections
5.8.2 Digital Input Connections – Fig 5.12
Six digital inputs are provided on Hybrid option boards.
Terminal Blocks C or D
1
di1
2
di2
3
di3
4
di4
5
di5
6
di6
7
COM
8
COM
Input State
Switch Input
Logic Input
(volt-free)
(TTL)
or
0V
or
5V
Fig. 5.12 Digital Input Connections
5.8.3 Analog Output Connections – Fig 5.13
Two analog outputs are provided on the Hybrid option board.
17
18
19
20
Fig. 5.13 Analog Output Connections
5 INSTALLATION
Load
15kΩ max.
or
5V
0V
Logic State
Dxx active
Dxx inactive
+
a01
+
a02
85

Advertisement

Table of Contents
loading

Table of Contents