2. INSTALLATION
(b) Installation of two or more servo amplifiers
Leave a large clearance between the top of the servo amplifier and the cabinet walls, and install a
cooling fan to prevent the internal temperature of the cabinet from exceeding the environment.
When mounting the servo amplifiers closely, leave a clearance of 1 mm between the adjacent servo
amplifiers in consideration of mounting tolerances. In this case, keep the ambient temperature within
0 ˚C to 45 ˚C or use the servo amplifier with 75% or less of the effective load ratio.
Cabinet
100 mm or more
30 mm
or more
40 mm or more
(Note 1)
Leaving clearance
Note 1. For the 11 kW to 22 kW servo amplifiers, the clearance between the bottom and the ground will be 120 mm or more.
2. When mounting MR-J4-500_-RJ, maintain a minimum clearance of 25 mm between the MR-J4-500_-RJ and a servo amplifier
mounted on the left side.
(2) Others
When using heat generating equipment such as the regenerative option, install them with full
consideration of heat generation so that the servo amplifier is not affected.
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
POINT
Close mounting is possible depending on the capacity of the servo amplifier. For
the possibility of close mounting, refer to each servo amplifier instruction
manual.
When closely mounting multiple servo amplifiers, the servo amplifier on the right
must have a larger depth than that on the left. Otherwise, the CNP1, CNP2, and
CNP3 connectors cannot be removed.
10 mm or more
(Note 2)
30 mm
or more
Cabinet
1 mm
Mounting closely
2 - 3
100 mm or more
1 mm
40 mm or more
30 mm
or more
Top
Bottom