ABB AC31 Assembly And Operation Manual page 155

Hide thumbs Also See for AC31:
Table of Contents

Advertisement

Data
Averaging of measured values
Resolution
Unused voltage inputs
Overvoltage protection
Overload range
Max. line length of analog lines, line
cross section > 0.14 mm²
*) Conversion cycle of MCU of I/O processing. The transmission via serial buses is slower.
Table 100: Analog output
Data
Number of channels
Connections
Reference connections (GND)
Type of outputs
Electrical isolation
Nominal range
Output load capability
Indication of the output signals
Resolution
Total errors (due to non-linearity,
offset, resolution and temperature)
Update cycle
Unused output
Short-circuit-proof
External supply protection
Max. line length of analog lines, line
cross section > 0.14 mm²
2018/09/24
For further information, please refer to the existing documentation
System description Advant Controller 31.
For further information, please refer to the existing documentation
System description Advant Controller 31.
3ADR010122, 8, en_US
Replacement devices: I/O modules > Replacement unit DC501-CS31-AD
Value
not available
8 bit
Can remain open or be short-circuited after GND or V+
to increase noise immunity
Available
± 30 V DC
100 m
Value
1
X3 / 6
X3 / 2, X3 / 7
Voltage unipolar
not available
0 ... 10 V
max. ± 5 mA
Replacement device: Not available
Existing device AX501: green LED per channel
8 bit
Replacement device: max. 3 %
Existing device AX501: 0.6 % ± 1 digit ± 150 ppm/K
1.5 ms
remains unconnected
Yes *)
Up to +30 V DC (no external supply protection available
for negative voltages!)
100 m
AC31 Adapters
155