ABB AC31 Assembly And Operation Manual page 20

Hide thumbs Also See for AC31:
Table of Contents

Advertisement

AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD
Please observe the system data for CS31 bus
system data" on page 4.
For general information on the CPU, please refer to the AC500 documentation.
1.4.1.2
Central unit 07KT98
1.4.1.2.1
Short description
The central unit 07KT9x-AD acts as
bus master in the decentralized automation system.
Slave operation is not possible.
Advant Controller 31 or as stand-alone central unit.
Main features
16 digital inputs with LED display.
Caution! Electrical isolation/potential reference has changed.
16 digital outputs with LED display.
Caution! Electrical isolation/potential reference has changed.
16 digital inputs/outputs with LED display.
Caution! Electrical isolation/potential reference has changed.
8 individually configurable analog inputs. Available modes
tion of the 8 configurable analog inputs" on page 32.
Caution! Electrical isolation/potential reference has changed.
4 individually configurable analog outputs.
Caution! Electrical isolation/potential reference has changed.
2 counters for counting frequencies up to 50 kHz, configurable in 10 different modes.
Caution! Each counting input requires an external resistor of 470 Ω / 1 W that is con-
nected upstream. The potential reference has changed.
1x serial interface COM2
1x serial diagnosis interface DIAG
Caution! No electrical isolation to supply voltage L+/M.
LED LCD display to indicate operating conditions and error messages
Fastening by screws or snapping onto top-hat rail
Lithium battery TA521
Various operating buttons for user input
Comprehensive diagnosis functions
Integrated Flash EPROM, RAM and memory for storing programs and data
Exchangeable SD memory card MC502
20
In addition to the CPU, the replacement devices 07KT9x-AD are based on the
modules DA501 and DA502 of the AC500 series. All I/O channels are protected
against reverse polarity, reverse supply, short circuit and continuous overvol-
tages up to 30 V DC. For further information on these modules, please refer to
the AC500 documentation.
The description of the protective functions, error indications and diagnosis
options contained in the existing documentation are no longer valid. Please
refer to the AC500 documentation (DA501-/ DA502 modules and CPU) con-
cerning this information.
Modbus RTU, master and slave
An online access (RS-232 programming interface for PC/Automation Builder)
A free protocol (communication via the blocks COM_SEND and COM_REC)
3ADR010122, 8, en_US
Ä Chapter 1.3 "System data and CS31 bus
Ä Chapter 1.4.1.3.1.7 "Connec-
2018/09/24

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents