ABB AC31 Assembly And Operation Manual page 50

Hide thumbs Also See for AC31:
Table of Contents

Advertisement

AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD
Data
Resolution in bits:
-> Ranges
-> Ranges
-> Range
Resolution in mV, μA:
-> Range
-> Range
-> Range
-> Range
Relationship between input signal and hex
code
Conversion error of the analog values due to
non-linearity.
Adjustment error on delivery and resolution in
the nominal range
Use as digital input:
-> Signal 0
-> Undefined signal state
-> Signal 1
Max. cable length
2-core shielded and conductor cross section >
0.14 mm²
Analog outputs
Data
Number of channels per device
Connections
Reference potential
50
CAUTION!
Risk of overloading the analog input!
If an analog current sensor supplies a current in excess of 25 mA for more than
1 second during initialization, this input is switched off by the module (input pro-
tection).
Use only sensors with fast initialization or sensors without current peaks higher
than 25 mA. If this is not possible, protect the input by connecting a 10-volt
zener diode in parallel to I+ and I-.
For further information, please refer to the existing documentation
System description Advant Controller 31.
3ADR010122, 8, en_US
Value
±10 V, 0 ... 10 V 12 bit plus sign
0 ... 20 mA, 4 ... 20 mA 12 bit without sign
Pt100, Pt1000, Ni1000: 0.1 °C
±10 V approx. 2.5 mV
0 ... 10 V approx. 2.5 mV
0 ... 20 mA approx. 5 μA
4 ... 20 mA approx. 4 μA
-100 % ... 0 ... +100 % = 9400H ... 0000H ...
6C00H (-27648 ... 0 ... 27648 decimal)
Typ. 0.5 %, max. 1 %
-30 V ... +5 V
+5 V ... +13 V
+13 V ... +30 V
100 m
Value
4
Connector X10 (terminals 3.5, 3.6, 7.5 and
7.6)
AGND2 (terminals 3.5, 3.6, 7.5 and 7.6)
2018/09/24