1.5.1.8.2
Technical Data of the Digital Inputs
Data
Connections
Input type according to EN 61131-2
Input delay: 0 -> 1 or 1 -> 0 *)
Indication of the input signals
Input signal voltage:
-> 0 signal
-> Undefined signal
-> 1 signal
-> Residual ripple at 0 signal
-> Residual ripple at 1 signal
Input current per channel:
Input voltage +24 V
Input voltage +5 V
Input voltage +15 V
2018/09/24
For further information, please refer to the existing documentation
System description Advant Controller 31.
CAUTION!
System damage caused by voltage!
Exceeding the maximum supply or process voltage (>30 V DC) results in per-
manent system damage (destruction).
3ADR010122, 8, en_US
Replacement devices: I/O modules > Replacement device 07DC91-AD
Value
X2/1.0, X2/1.1, X2/1.2, X2/1.3, X2/1.4, X2/1.5,
X2/1.6, X2/1.7, X3/2.0, X3/2.1, X3/2.2, X3/2.3,
X3/2.4, X3/2.5, X3/2.6, X3/2.7
Type 1 (realized through current sink)
Replacement device: Typ. 8 ms
Existing device: Typ. 7 ms
Replacement device: One yellow LED per
channel. The LED corresponds functionally to
the input signal.
Existing device: One green LED per channel.
The LED corresponds functionally to the input
signal.
24 V DC
Replacement device: -3 V...+5 V
Existing device: -30 V...+5 V
Replacement device: > +5 V...< +15 V
Existing device: > +5 V...< +13 V
Replacement device: +15 V...+30 V
Existing device: +13 V...+30 V
Replacement device: within -3 V...+5 V
Existing device: within -30 V...+5 V
Replacement device: within +15 V...+30 V
Existing device: within +13 V...+30 V
Replacement device: Typ. 5 mA
Existing device: Typ. 7 mA
Replacement device: > 1 mA
Existing device: ³ 1 mA
Replacement device: > 5 mA
Existing device: ³ 2 mA (at input voltage +13
V)